Transformer insulation film physical properties testing verifies the mechanical strength, dimensional stability, and long-term durability of insulating films used in dry-type and oil-immersed transformers. This technical guide covers the key physical test items, including thickness, tensile strength, elongation at break, heat shrinkage, tear resistance, folding endurance, and moisture absorption, together with the internationally recognized IEC, ISO, ASTM, and GB test methods applied by accredited third-party laboratories. Use this article to strengthen incoming inspection, design verification, and failure analysis programs for transformer insulation films.
Technical Overview
Insulation films are critical components in both dry-type and oil-immersed transformers, where they function as interlayer insulation, interwinding barriers, wire wrap insulation, and core-to-ground separation. Throughout the service life of a transformer, these films must withstand winding tension during manufacture, impregnation forces, continuous thermal cycling, mechanical vibration, and electrodynamic stress during fault events. A film with inadequate physical properties can crack, shrink, or delaminate long before its electrical properties become marginal, making physical characterization a frontline indicator of insulation system reliability.
The most widely used insulation films include biaxially oriented polyester (BOPET) films, polyimide (PI) films for high-temperature Class H and Class C applications, polyethylene naphthalate (PEN) films, cellulose-based papers and pressboard for oil-filled units, aramid fiber sheets, and flexible composite laminates that combine polymer films with fibrous substrates. Each material class carries its own specification and acceptance requirements, but all are evaluated against a common framework of mechanical and dimensional test methods published by IEC, ISO, ASTM, and GB standards organizations.
Physical properties testing is typically performed by accredited third-party laboratories or in-house quality departments following strict specimen conditioning, typically 23 °C and 50% relative humidity per ISO 291 or ASTM D618. The core methodological references include IEC 60674-2 for plastic films for electrical purposes, ISO 527-3 and ASTM D882 for tensile properties, ASTM D1204 for heat shrinkage, and the GB/T 13542 series, which aligns Chinese national requirements with the IEC framework.
Testing Samples
Polyester (PET) Insulation Films
Biaxially oriented PET films in the range of approximately 20 µm to 350 µm are the workhorse of distribution transformer insulation. They are tested as received in roll or sheet form, with specimens cut in both the machine direction (MD) and transverse direction (TD) to capture the anisotropy introduced by biaxial orientation.
Polyimide (PI) Insulation Films
Polyimide films, typically 7.5 µm to 125 µm, are used where continuous operating temperatures exceed the capability of PET, including traction and inverter-fed transformer applications. Corona-resistant polyimide grades are additionally evaluated for mechanical integrity after thermal aging, since filler systems can affect flexibility.
Cellulose and Pressboard Materials
For oil-immersed transformers, cellulose-based films, papers, and pressboard laminates are tested for tensile strength, tearing resistance, bursting strength, and moisture content. Because cellulosic materials are hygroscopic, samples must be sealed and stored under controlled conditions before testing to prevent moisture pickup that would distort results.
Aramid Fiber Sheets
Meta-aramid and para-aramid sheets used in high-temperature dry-type transformers are characterized for tensile and tear behavior under IEC 60819 framework requirements for non-cellulosic fibrous insulation materials.
Flexible Composite Laminates
Multi-layer composites, such as polymer film laminated with aramid nonwoven layers or with a second film layer via adhesive, are tested both as finished laminates and, where relevant, as individual layers. Delamination resistance and retained strength after heat exposure are key acceptance considerations.
Testing Items
A comprehensive physical properties test program for transformer insulation films generally includes the following items, selected according to the material specification and end-use thermal class:
- Thickness and thickness tolerance across the web
- Tensile strength in machine direction and transverse direction
- Elongation at break in both directions
- Tensile modulus (Young's modulus)
- Heat shrinkage after defined thermal exposure
- Tear resistance, both initial and propagating
- Folding endurance (MIT double folds)
- Bursting strength for fibrous papers and boards
- Water absorption and equilibrium moisture content
- Density for material identification and lot consistency
- Thermal characteristics such as glass transition and melting behavior
- Surface properties, including roughness and coefficient of friction where winding processability is critical
Testing Methods
Each test item is executed under a defined international or national standard, with specimen geometry, conditioning, and calculation rules that must be strictly followed for comparable results.
Specimen Conditioning
Prior to mechanical testing, film specimens are conditioned at 23 ± 2 °C and 50 ± 5% relative humidity for a minimum of 40 hours in accordance with ISO 291 or ASTM D618 Procedure A. Cellulosic samples that require dry-basis reporting are oven-conditioned and tested rapidly after removal from desiccation to limit reabsorption.
Thickness Measurement
Thickness is measured with a dead-weight micrometer or precision linear gauge having a defined foot diameter and contact pressure, following ISO 4593, ASTM D374, or IEC 60674-2. Measurements are taken at multiple positions across the width and length of the web, since localized thin spots directly reduce dielectric margin in service.
Tensile Strength and Elongation at Break
Tensile testing is performed on strip specimens using a universal testing machine per ISO 527-3 or ASTM D882, with gauge lengths typically of 100 mm for ISO and 50 mm or 100 mm for ASTM, and crosshead speeds selected according to the expected elongation. Results are reported as tensile strength in MPa and elongation at break in percent, separately for MD and TD. Retained tensile strength is also the primary diagnostic property in thermal endurance evaluations under the IEC 60216 series.
Tear Resistance
Propagating tear resistance is determined with an Elmendorf-type tester per ASTM D1922 or ISO 6383-2, while initial tear resistance may be measured by the trouser or Graves geometry per ISO 6383-1 or ASTM D1004. Tear performance is particularly important for films that must survive sharp conductor edges and slot corners during winding.
Folding Endurance
Folding endurance is measured on a MIT-type folding instrument, commonly following ISO 5626 methodology adapted for films. The result, expressed as the logarithm of the number of double folds to failure, is a sensitive indicator of embrittlement and is widely tracked before and after thermal aging studies.
Heat Shrinkage and Dimensional Stability
Dimensional change on heating is determined per ASTM D1204 or ISO 11501 by exposing marked specimens to a specified temperature, for example 150 °C for 30 minutes for many PET film grades, and calculating the percentage length change in both directions. Excessive shrinkage can loosen winding packages and reduce creepage distances in assembled transformers.
Water Absorption and Moisture Content
Water absorption of polymer films is measured by 24-hour immersion at 23 °C per ISO 62 or ASTM D570 and reported as percentage mass gain. For cellulose materials, moisture content is determined gravimetrically by oven drying at 105 °C, since moisture in cellulosic insulation accelerates aging and degrades dielectric performance in oil-filled transformers.
Density and Thermal Analysis
Density is determined by the immersion method per ISO 1183-1 or by density-gradient column per ASTM D1505, supporting material identification and detection of lot-to-lot variation. Differential scanning calorimetry per ISO 11357 is used to verify glass transition temperature, melting behavior, and crystallinity, which helps identify contamination, wrong resin grade, or excessive reprocessed content.
Applications
Physical properties testing of transformer insulation films supports multiple engineering and business functions across the transformer value chain:
- Incoming quality control at transformer and coil manufacturers, verifying that film lots conform to purchase specifications before winding operations begin
- Material qualification and design verification when introducing new insulation systems, thermal classes, or suppliers
- Thermal aging and lifetime assessment programs in which tensile strength and folding endurance are tracked as degradation endpoints under the IEC 60216 framework
- Root-cause and failure analysis after in-service insulation breakdown, cracking, or shrinkage incidents
- Factory production control at film manufacturers for release testing against IEC 60674, GB/T 13542, and customer-specific specifications
- Compliance support for insulation system recognition, including evaluation under frameworks such as UL 1446 and the material requirements referenced in IEC 60076-11 for dry-type transformers
FAQ
Which standards govern transformer insulation film physical testing?
The core method standard for plastic electrical insulation films is IEC 60674-2, complemented by ISO 527-3 or ASTM D882 for tensile properties, ASTM D1922 or ISO 6383 for tear resistance, ASTM D1204 or ISO 11501 for heat shrinkage, ISO 62 or ASTM D570 for water absorption, and ISO 4593 or ASTM D374 for thickness. In China, the GB/T 13542 series adopts the corresponding requirements for electrical insulation films.
Why must tensile properties be tested in both machine and transverse directions?
Most transformer films, especially biaxially oriented PET and polyimide, are deliberately anisotropic. Strength, elongation, shrinkage, and tear behavior can differ substantially between the machine direction and transverse direction, and winding stress is applied differently in each orientation. Testing both directions ensures the film meets specification under real loading conditions.
What conditioning is required before testing?
Polymer film specimens are conditioned at 23 ± 2 °C and 50 ± 5% relative humidity for at least 40 hours per ISO 291 or ASTM D618 Procedure A. Cellulosic materials may require sealed storage and dry-basis measurement because their properties are strongly moisture dependent.
What are typical acceptance levels for common properties?
Acceptance criteria are grade specific and defined in the applicable material specification. As general reference points, biaxially oriented PET films commonly exhibit tensile strength in the range of roughly 180 to 260 MPa with elongation at break of 70% to 160%, polyimide films typically show tensile strength of about 130 to 230 MPa with elongation of 25% to 70%, and heat shrinkage limits of 1.5% to 3.5% after standard thermal exposure are frequently specified. Certified values must always be taken from the governing specification sheet.
How does physical testing complement dielectric testing?
Physical degradation usually precedes electrical failure. A film can retain acceptable dielectric breakdown strength while its tensile strength and folding endurance have already declined significantly, indicating embrittlement that will lead to cracking under mechanical or thermal stress. A robust program therefore combines physical tests with electrical measurements, such as dielectric breakdown voltage per IEC 60243-2 and volume resistivity, to give a complete picture of insulation condition.
How much sample is needed and how long does testing take?
Tensile testing typically requires at least five to ten strip specimens per direction, and full physical test suites can usually be completed from a few A4-sized sheets of film. At accredited third-party laboratories, routine physical property testing is commonly completed within five to seven working days, while aging studies extending over weeks or months are scheduled according to the selected exposure conditions.